Mode of operation
The actuator is controlled with a standard signal of DC 0 ... 10 V and moves the damper to the operating position while tensioning the return spring at the same time. The damper is turned back to the safety position by spring energy when the supply voltage is interrupted.

Thermoelectric tripping device
If the ambient temperature of 72°C is exceeded, the thermal fuse Tf1 responds.
If the duct inside temperature of 72°C is exceeded, the exchangeable thermal fuse Tf2/Tf3 will respond.
When the thermal fuses Tf1, Tf2 or Tf3 respond, the supply voltage is interrupted permanently and irreversibly.
The LED is lit when
– there is a supply voltage,
– the temperature fuses are OK and
– the test switch is not pressed.
The function of the thermal fuse and the test button is only warranted if the actuator is connected to the power supply and has reached its operating position (LED on).

Signalling
Two microswitches with fixed settings are installed in the actuator for indicating the damper end positions.
The position of the damper blade can be read off on a mechanical position indicator.

Manual operation
Without power supply, the damper can be operated manually and fixed in any required position. It can be unlocked manually or automatically by applying the supply voltage. If manual operation is used when supply voltage is present, the actuator first moves to the safety position for checking and then to the position as defined by positioning signal Y. During this self-check, the motor running time is increased to 100 s and the measuring voltage remains at 2 V.

Технические характеристики

Electrical data
Nominal voltageAC/DC 24 V
Nominal voltage frequency50/60 Hz
Nominal voltage rangeAC 19.2 V ... 28.8 V / DC 21.6 V ... 28.8 V
Power consumption in operation7 W
Power consumption at rest2 W
Power consumption for wire sizing9.5 VA
Power consumption for wire sizing noteImax 8.3 A @ 5 ms
Auxiliary switch2 x SPDT
Switching capacity auxiliary switchContact gold-plated silver: 1 mA … 3 (0.5) A, DC 5 V … AC 250 V (II Totally insulated)
Switching points auxiliary switch5° / 80°
Connection supply / controlCable 1 m, 4 x 0.75 mm² (halogen-free)
Connection auxiliary switchCable 1 m, 6 x 0.75 mm² (halogen-free)
Cable length thermoelectric tripping device1 m
Functional data
Torque motorMin. 18 Nm
Torque spring-returnMin. 12 Nm
Control signal Y DC0 V ... 10 V
Control signal Y noteInput impedance 100 kΩ (0.1 mA)
Operating range Y DC2 V ... 10 V
Operating range Y noteFor control signal Y
Position feedback U DC2 V ... 10 V
Position feedback U noteMax. 0.5 mA (for 0 … 100% angle of rotation)
Position accuracyn±5%
Direction of rotation motorCan be selected by mounting L / R
Angle of rotationMax. 95°
Running time motor‹120 s / 90°
Running time spring-return16 s (tamb = 20°C)
Sound power level motor max.45 dB (A)
Sound power level spring-return max.63 dB (A)
Damper rotationForm fit 12 mm (10 mm with enclosed adapter)
Position indicationMechanically, with pointer
Service lifeMin. 60,000 safety positions
Safety
Response temperature thermal fuseTf1: Duct outside temperature 72°C Tf2 and Tf3: Duct inside temperature 72°C
Protection class IEC/ENIII Safety extra-low voltage
Degree of protection IEC/ENIP54 in all mounting positions
EMCCE according to 2014/30/EU
Low-voltage directiveCE according to 2014/35/EU
Certification IEC/ENCertified according to IEC/EN 60730-1 and IEC/EN 60730-2-14
Mode of operationType 1.AA.B
Rated impulse voltage supply / control0.8 kV
Control pollution degree3
Ambient temperature normal duty-30°C … 50°C
Ambient temperature safety duty The safety position will be attained up tomax. 75°C
Non-operating temperature-40°C ... 50°C
Ambient humidity95% r.h., non-condensing
MaintenanceMaintenance-free
Weight
Weightapprox. 2.8 kg