Mode of operation
2-wire open-close control. The actuator is overload-proof and can thus remain energised even at  the end stops.

Signalling
Two microswitches with fixed settings are installed in the actuator for indicating the damper end positions. The position of the damper blade can be read off on a mechanical position indicator.

Manual operation
The hand crank supplied with the actuator can be used for manual operation.The damper function can thus be tested easily.

Standards / regulations

•  Draft DIN 18232, Part 6, September 1992

–  Fire protection in industrial buildings
–  Smoke and heat extraction systems

•  Preliminary standard ÖNORM H 6029, May  1997
  Ventilation systems
  –  Fire smoke extraction systems
  Excerpts from:
  –  CEN/TC191, 1996
  –  NA BAU, 1997

Технические характеристики

Electrical data
Nominal voltageAC 230 V, 50/60 Hz
Power supply rangeAC 198 ... 264 V
Switching thresholds
Min. ON voltage
Max. OFF voltage
AC 198 V
AC 100 V
Power consumption
Operation
End position
Rating
7 W @ nominal torque
0.5 W
14 VA / lmax. 8.2 A at 5 ms
Auxiliary switch
Contact rating (silver contact)
(gold-plated silver contact)
Switching points
Tolerance
2 x 1 PDT
6 (3) A, AC 250 V
1 mA ... 6 A, DC 5 V ... AC 250 V
3° / 87° (referring to 0 ... 90°)
±2°
Connection
Motor
Auxiliary switch
Cable 1 m, 3 x 2 mm2 (halogen-free)
Cable 1 m, 6 x 2 mm2 (halogen-free)°
Functional data
Torque (nominal torque)Min. 15 Nm at nominal voltage
Inhibiting torque
Dynamic
Static
15 Nm
18 Nm
Direction of rotationCan be selected by mounting L / R
Angle of rotationMax. 95° (incl. 5° mechanical overrun)
Running time‹30 s for 90°
Sound power levelMax. 60 dB (A)
Damper rotation12 mm form-fit
Position indicationMechanical with pointer
Service lifeMin. 10 000 cycles
Safety
Protection classII totally insulated
Degree of protectionIP54 in all mounting positions
EMCCE acc. to 2004/108/EC
low-voltage directiveCE according to 2006/95/EC
Mode of operationType 1.C (EN 60730-1)
Rated impulse voltage4 kV
Control pollution degree3
Ambient temp. range
Standard operation
> Safety function
-30 ... +50°C
See «Safety function»
Non-operating temperature range-40 ... +80°C
Ambient humidity rangeAccording to EN 60730-1
MaintenanceMaintenance-free
Dimensions / weigh
DimensionsSee «Dimensions» on page 3